ТЕПЛОВОЙ НАСОС EASYPACK-I TCAIY-THAIY 270÷2130

DESCRIPTION

RHOSS EXP ISO 9001RHOSS EXP EUROVENT

Chillers and heat pumps with inverter compressors

  • Precise and efficient load modulation;
  • Plug-and-play unit with integrated hydraulic module and heat recovery unit;
  • Built-in MASTER SLAVE control board function.

Design features:

  • Compressor: Hermetic rotary scroll compressor with thermal protection and crankcase heating element, inverter driven (1+i);
  • Continuously adjustable with high efficiency at partial loads;
  • Water heat exchanger: Stainless steel plates with closed-cell polyurethane foam rubber insulation and a differential water flow pressure switch;
  • Air heat exchanger: microchannel or finned coil with copper tubes and aluminum fins, depending on the model/size;
  • Fan: axial electric fans with external rotor and internal thermal protection and safety grilles. Depending on the size, electric fans can be EC type or equipped with an electronic proportional device for continuous speed control;
  • Control: Electronic, microprocessor-based, with Adaptive Function Plus logic system;
  • Construction: The supporting structure is made of galvanized sheet steel and coated with polyester powder paint.

The unit also includes^

  •  thermal-magnetic switches, compressors, and fans;
  •  electronic expansion valve;
  • Display of high and low pressure in the cooling circuit;
  •  Master/Slave control for up to 4 units in parallel;
  • Clock sensor board.

Available versions:

  • Т - High-efficiency version with an enlarged condensate section (TCAITY-THAITY);
  • Q - Enhanced soundproofing version, including soundproofing for the technical compartment, low-speed fans, and an enlarged condensate section (TCAIQY-THAIQY).

Models:

  • TCAITY: High-efficiency cooling-only unit;
  • TCAIQY: Highly sound-insulated cooling-only unit;
  • THAITY: Heat pump unit;
  • THAIQY: Highly sound-insulated heat pump unit.
  MODEL TCAITY-TCAIQY   270 280 290 2100 2115 2130
Cooling capacity кВт 69,8 82,6 90,3 97,9 117 130,4
Cooling capacity kW 67,8 80,8 87,7 93,4 111,4 125,5
E.E.R.   3,16 3,17 3,15 3,02 3,1 3,14
E.E.R.   3,01 3,06 3 2,84 2,9 3,01
Power consumption kW 22,09 26,06 28,67 32,42 37,74 41,53
Power consumption kW 22,52 26,41 29,23 32,89 38,41 41,69
  MODEL THAITY-THAIQY   270 280 290 2100 2115 2130
Thermal rated power kW 73,4 85,4 92,5 100,6 121,5 134,6
Thermal rated power kW 71,2 83,4 90,4 98,7 117,4 130,6
C.O.P.   3,37 3,34 3,36 3,34 3,37 3,32
C.O.P.   3,31 3,33 3,32 3,3 3,34 3,36
Cooling capacity kW 67,1 79,3 86,8 93,5 112,6 126,5
Cooling capacity kW 65 77,9 84,7 90,3 108,6 123,5
Power consumption kW 21,78 25,57 27,53 30,12 36,05 40,54
Power consumption kW 21,51 25,05 27,23 29,91 35,15 38,87
  MODEL TCAIY-THAIY   270 280 290 2100 2115 2130
TCAITY-THAITY sound pressure dB(A) 52 53 53 53 55 56
TCAIQY-THAIQY sound pressure dB(A) 45 46 46 46 49 50
TCAITY-THAITY sound power dB(A) 84 85 85 85 87 88
TCAIQY-THAIQY sound power dB(A) 77 77,5 77,5 77,5 81 82
  Scroll/step compressor n. 1+i / НЕПРЕРЫВНАЯ РЕГУЛИРОВКА 1+i / НЕПРЕРЫВНАЯ РЕГУЛИРОВКА 1+i / НЕПРЕРЫВНАЯ РЕГУЛИРОВКА 1+i / НЕПРЕРЫВНАЯ РЕГУЛИРОВКА 1+i / НЕПРЕРЫВНАЯ РЕГУЛИРОВКА 1+i / НЕПРЕРЫВНАЯ РЕГУЛИРОВКА
  Contours n. 1 1 1 1 2 2
  Power supply V-Ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
  DIMENSIONS AND WEIGHT   270 280 290 2100 2115 2130
  L - Width mm 3250 3250 3250 3250 3450 3450
  H - Height mm 1540 1540 1540 1540 2000 2000
  P - Depth mm 1210 1210 1210 1210 1520 1520
Weight TCAITY kg 765 790 795 800 1125 1145
Weight THAITY kg 880 915 920 925 1325 1345


Data under the following conditions:
❶    Air: 35°C - Water: 12/7°C.
❷    Air: 7°C, D.B. - 6°C W.B. - Water: 40/45°C.
❸    In an open field (Q = 2) at a distance of 10 m from the unit.
❹    Total sound power level in dB(A) based on measurements according to UNI EN-ISO 9614.
❺    Weight of empty unit.
TCAIQY-THAIQY super silent version.
Performance according to EN 14511:2018.