+38 044 379-12-05, (-07)

+38 044 379-12-05, (-07)

+38 044 379-12-05, (-07)

ВЕНТИЛЯЦИОННАЯ УСТАНОВКА UTNR-A PLATINUM 040÷500

DESCRIPTION
  • ErP 2018 NRVU compliant;
  • High-efficiency heat recovery units with Eurovent certification;
  • Multi-speed fans or EC brushless fans;
  • High-efficiency F7 and M5 filters;
  • Double sandwich panel with high insulating capacity;
  • Full Control kit.

Features:

  • Heat recovery unit: very high-performance static type, with cross-flow aluminum fins and comparable stroke. Side-extracting exchange package (except size 40 with bottom-extracting);
  • Fans: centrifugal air extraction, renewal, and exhaust fans with double suction and a directly coupled electric motor; optional high-efficiency electric motors with EC brushless technology. Fan housing mounted on vibration-damping mounts to prevent vibration transfer to the structure. EC fans can be factory-configured for constant flow operation (required at time of order).
  • Construction: Extruded aluminum frame with nylon joints. Prefabricated sandwich panels: 23 mm thick, internally galvanized sheet metal, pre-painted on the outside, with highly effective thermal and acoustic insulation made of injection-molded polyurethane with a density of 45 kg/m³, providing excellent thermal and acoustic insulation.
  • Filtering section: The filter sections consist of compact filters with low-pressure polypropylene cells, with side outlets, efficiency class F7 in the fresh air stream and M5 in the discharge stream.
  • Factory-installed differential pressure switches for filter clogging alarms.
  • Galvanized steel condensate collection tray with bottom drain;
  • Free-cooling or integrated defrost bypass system. A motorized damper on the heat recovery unit enables a bypass system for free-cooling or defrost control based on thermo-hygrometric requirements.

Available options:

  • UTNR-A/O PLATINUM - Heat recovery unit with a cross-flow heat exchanger, horizontal installation, and standard multi-speed fans;
  • UTNRE-A/O PLATINUM - Heat recovery unit with a cross-flow heat exchanger, horizontal installation, and brushless EC fans, capable of limiting ventilation power consumption while maintaining the same performance characteristics.

Available applications:

  • 01- Connection side on the right;
  • 02- Connection side on the left.

To complete your order, please specify the desired direction.

Installation:

  • EXT - Outdoor installation, including rain cover, 80mm high base, and external electrical box.

Detailed information can be found on the manufacturer’s website at www.rhoss.com or contact our specialists.