RHOSS EXP ISO 9001RHOSS EXP EUROVENT

T.E.R. (°) up to 7.8

Specifications:

  • Compressor: Hermetically sealed rotary scroll compressor with thermal protection and crankcase heating element;
  • Heat exchangers on the primary (user), secondary (recovery), and waste sides: with stainless steel cross-flow plates, closed-cell polyurethane foam rubber insulation, and a differential water flow pressure switch;
  • Control: Electronic, microprocessor-based, with Adaptive Function Plus logic system;
  • Construction: Galvanized sheet steel, powder-coated with polyester paint.

The unit also includes:

  • Compressor magnetic-thermal switches
  • Electronic expansion valve;
  • high and low pressure display for the cooling circuit;
  • clock board;
  • An outside air temperature sensor for setpoint compensation;
  • A 0-10 volt analog signal for condensation/evaporation control, implemented on an external device.

Versions:

  • B - Standard version.

Models:

  • TXHEBY: EXPsystems unit.
  TXHEBY MODEL   245 250 260 270 290 2115 2130 2145 2165 2185
Cooling capacity (AUTOMATIC 1) kW 47 55,6 62,7 71,8 92,8 123,8 137,5 153,9 173,3 193,2
Cooling capacity (AUTOMATIC 1) kW 44,2 52 59,2 67,6 88 114,6 128 142,4 161,7 180,6
Heat recovery capacity (AUTOMATIC 2) kW 50,8 59,9 68,9 76,6 103,5 135,4 149,4 165,4 188,5 212
Thermal rated power (SELECT 1-2 AUTOMATIC 3) kW 49,3 58,1 66,9 74,3 100,6 131,8 145,5 160,9 183,5 206,4
Total power consumption (AUTOMATIC 1) kW 8,5 9,8 11,3 13 16,9 21,5 24,7 26,7 31,8 36,3
Total power consumption (AUTOMATIC 1) kW 9,9 11,4 13,1 14,9 19,1 25,5 28,8 31,7 36,8 41,9
Total power consumption (AUTOMATIC 2) kW 12,2 14 16,1 17,8 24 31,6 35,4 39,5 46 52,3
Total power consumption (SELECT 1-2 AUTOMATIC 3) kW 12,1 13,9 15,9 17,6 23,7 31,4 35,14 39,1 45,6 52,1
E.E.R. (AUTOMATIC 1)   5,51 5,69 5,55 5,51 5,48 5,75 5,57 5,76 5,44 5,32
E.E.R. (AUTOMATIC 1)   4,49 4,57 4,52 4,54 4,61 4,5 4,45 4,5 4,4 4,32
C.O.P. (SELECT 1-2 AUTOMATIC 3)   4,07 4,19 4,2 4,21 4,25 4,2 4,14 4,11 4,02 3,96
T.E.R. (AUTOMATIC 2)   7,32 7,55 7,57 7,62 7,63 7,59 7,45 7,39 7,21 7,12
  TXHEBY MODEL   245 250 260 270 290 2115 2130 2145 2165 2185
Sound power dB(A) 67 67 68 68 70 72 73 74 74 75
  Scroll/step compressor no. 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2
  Contours no. 1 1 1 1 1 1 1 1 1 1
  Power supply V-Ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
       DIMENSIONS AND WEIGHT   245 250 260 270 290 2115 2130 2145 2165 2185
  L - Width mm 1020 1020 1020 1020 1020 1270 1270 1270 1270 1270
  H - Height mm 1470 1470 1470 1470 1470 1620 1620 1620 1620 1620
  P - Depth mm 870 870 870 870 870 870 870 870 870 870
Depth kg 510 525 540 565 595 920 960 995 1035 1045
  SEASONAL ENERGY INDICATORS   245 250 260 270 290 2115 2130 2145 2165 2185
  TXHEBY MODEL SEASONAL PERFORMANCE CHARACTERISTICS FOR HEATING                      
Pdesignh (EN 14825) kW 59 69 80 89 119 156 173 191 218 245
SCOP (EN 14825)   5,89 6,09 6,21 6,1 6 6,42 6,31 6,3 6,08 5,87
ηs % 228 236 240 236 232 249 244 244 235 227
  Energy efficiency class   A+++ A+++ - - - - - - - -


Data under the following conditions:
Chilled water (user): 12/7°C - Condenser water (source return): 14/30°C (Gross calorific value).
Chilled water (user): 12/7°C - Condenser water (source return): 30/35°C.
Chilled water (user): 12/7°C - Condenser water (heat recovery): 40/45°C. (Gross calorific value)
Evaporator water (source): 12/7°C - Hot water (user): 40/45°C.
Total sound power level in dB(A) based on measurements according to standard UNI EN-ISO 9614.
Weight of empty unit.
Performance according to EN 14511:2018.
T.E.R.: Overall Efficiency
Low temperature applied (7°C)
Seasonal Energy Efficiency Ratio: Low Temperature Cooling (Regulation (EU) 2016/2281)
Average Climate, Low Temperature applied (35°C)
Seasonal Energy Efficiency Ratio: Low Temperature

  TXHEBY MODEL   4180 4205 4235 4260 4290 4330 4360 4410 4450
Cooling capacity (AUTOMATIC 1) kW 188,5 214,7 241,2 270,2 302,7 341,1 379,9 420,9 462,6
Cooling capacity (AUTOMATIC 1) kW 176,4 201,7 226,7 253,6 280,2 317,9 354 397,1 437,8
Heat recovery capacity (AUTOMATIC 2) kW 203,2 232,2 260,6 293,8 327,1 372,5 418,8 469,3 520,2
Thermal rated power (SELECT 1-2 AUTOMATIC 3) kW 198,8 227,5 255,4 288 320 367 412,6 459,3 509,7
Total power consumption (AUTOMATIC 1) kW 32,2 37,2 41,9 46,6 50,4 59,1 67,2 78,9 90,4
Total power consumption (AUTOMATIC 1) kW 37,4 42,9 48,2 54,1 60,2 69,3 79,1 90,5 102,8
Total power consumption (AUTOMATIC 2) kW 44,2 51,5 58,8 66,1 73,7 85,4 96,9 110,5 124,7
Total power consumption (SELECT 1-2 AUTOMATIC 3) kW 43,9 51,1 58,4 65,6 72,9 84,6 95,9 109,4 123,1
E.E.R. (AUTOMATIC 1)   5,85 5,77 5,76 5,8 6,01 5,77 5,65 5,33 5,12
E.E.R. (AUTOMATIC 1)   4,72 4,71 4,71 4,69 4,66 4,59 4,48 4,39 4,26
C.O.P. (SELECT 1-2 AUTOMATIC 3)   4,52 4,45 4,37 4,39 4,39 4,34 4,3 4,2 4,14
T.E.R. (AUTOMATIC 2)   8,2 8,03 7,87 7,89 7,87 7,73 7,64 7,49 7,34
  TXHEBY MODEL   4180 4205 4235 4260 4290 4330 4360 4410 4450
Sound power dB(A) 77 77 78 79 80 81 82 83 84
  Scroll/step compressor no. 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
  Contours no. 2 2 2 2 2 2 2 2 2
  Power supply V-Ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
       DIMENSIONS AND WEIGHT   4180 4205 4235 4260 4290 4330 4360 4410 4450
  L - Width mm 2600 2600 2600 2600 2600 2600 2600 2600 2600
  H - Height mm 1860 1860 1860 1860 1860 1860 1860 1860 1860
  P - Depth mm 870 870 870 870 870 870 870 870 870
Weight kg 1690 1730 1780 1820 1890 1960 2000 2070 2100
  SEASONAL ENERGY INDICATORS   4180 4205 4235 4260 4290 4330 4360 4410 4450
  TXHEBY MODEL SEASONAL COOLING PERFORMANCE CHARACTERISTICS                    
Pdesignc (EN 14825) kW - - - - - 317,9 353,9 397 437,8
SEER  (EN 14825)   - - - - - 5,96 5,83 5,66 5,95
ηs % - - - - - 230 225 218 230
  TXHEBY MODEL SEASONAL PERFORMANCE CHARACTERISTICS FOR HEATING                    
Pdesignh (EN 14825) kW 234 267 300 340 379 - - - -
SCOP (EN 14825)   6,72 6,62 6,5 6,56 6,65 - - - -
ηs % 261 257 252 255 258 - - - -


Data based on the following conditions:
Chilled water (user): 12/7°C - Condenser water (source return): 14/30°C (Gross calorific value).
Chilled water (user): 12/7°C - Condenser water (source return): 30/35°C.
Chilled water (user): 12/7°C - Condenser water (heat recovery): 40/45°C (Gross calorific value).
Evaporator water (source): 12/7°C - Hot water (user): 40/45°C.
Total sound power level in dB(A) based on measurements according to standard UNI EN-ISO 9614.
Weight of empty unit.
Performance according to EN 14511:2018.
T.E.R.: Overall Efficiency
Low temperature applied (7°C)
Seasonal Energy Efficiency Ratio: Low Temperature Cooling (Regulation (EU) 2016/2281)
Average Climate, Low Temperature applied (35°C)
Seasonal Energy Efficiency Ratio: Low Temperature Heating in Average Climate (Regulations (EU) Nos. 811/2013 and 813/2013)