+38 044 379-12-05, (-07)

+38 044 379-12-05, (-07)

+38 044 379-12-05, (-07)

МНОГОЦЕЛЕВАЯ СИСТЕМА EXP Y-PACK EXP TXAEY 280÷4320

DESCRIPTION

RHOSS EXP ISO 9001RHOSS EXP EUROVENT

T.E.R. (°) up to 8.18

Design Features:

  • Compressor: Hermetically sealed rotary scroll compressor with thermal protection and crankcase heating element;
  • Primary and secondary heat exchangers: Stainless steel cross-flow plates with an anti-freeze heating element, rubber insulation made of closed-cell polyurethane foam, and a differential water flow pressure switch included;
  • Air-side heat exchanger: finned coil with copper tubes and aluminum fins;
  • Fan: screw-type electric fans with EC motors, continuously variable speed control, equipped with internal thermal protection and safety grilles;
  • Control: electronic microprocessor-based control with Adaptive Function Plus logic system;
  • Construction: galvanized sheet steel, powder-coated with polyester paint.

The unit also includes:

  • Thermal magnetic switches, compressors, and fans;
  • clock circuit board;
  • electronic expansion valve;
  • refrigerant circuit high/low pressure display.

Available versions:

  • T - High-efficiency version with EC motor fans;
  • S - Soundproofed version, includes soundproofing for the technical compartment, compressors, and fans with EC motors at reduced speed.

Models:

  • TXAETY: EXPsystems unit;
  • TXAESY: EXPsystems unit with sound insulation.
  TXAETY MODEL   280 2100 2130 4160 4200 4260 4320
Cooling capacity (AUTOMATIC 1) kW 83,7 107,6 134,6 162,5 206,2 263,1 332,9
Heat recovery capacity (AUTOMATIC 2) kW 108 140 174 215 272 346 440
Thermal rated power (SELECT 1-2 AUTOMATIC 3) kW 86,3 111,4 139,5 171,6 227,9 282 354,3
Power consumption (AUTOMATIC 1) kW 27 35,2 43,8 56,6 72,6 93,9 118,5
Power consumption (AUTOMATIC 2) kW 23,6 32,2 39,3 51,5 65,2 81,4 106,5
Power consumption (SELECT 1-2 AUTOMATIC 3) kW 25,6 33,9 42,9 55,2 73,9 91,9 116,5
  E.E.R. (AUTOMATIC 1)   3,1 3,06 3,07 2,87 2,84 2,8 2,81
  T.E.R. (AUTOMATIC 2)   8,18 7,76 7,89 7,36 7,39 7,53 7,36
  C.O.P. (SELECT 1-2 AUTOMATIC 3)   3,37 3,29 3,25 3,11 3,08 3,07 3,04
Sound pressure dB(A) 52 52 53 54 59 61 61
Sound power dB(A) 84 84 85 86 91 93 93
  TXAESY MODEL   280 2100 2130 4160 4200 4260 4320
Cooling capacity (AUTOMATIC 1) kW 80,7 103,7 129,6 156,5 199,3 254,1 316
Heat recovery capacity (AUTOMATIC 2) kW 108 140 174 215 272 346 440
Thermal rated power (SELECT 1-2 AUTOMATIC 3) kW 84,3 108,4 136,4 167,6 221,8 275 345,2
Power consumption (AUTOMATIC 1) kW 27,3 35,6 44,3 57,2 73,6 94,9 119,3
Power consumption (AUTOMATIC 2) kW 23,6 32,2 39,3 51,5 65,2 81,4 106,5
Power consumption (SELECT 1-2 AUTOMATIC 3) kW 24,6 32,5 41,1 52,9 71,1 88,5 111,8
  E.E.R. (AUTOMATIC 1)   2,96 2,92 2,93 2,74 2,71 2,68 2,65
  C.O.P. (SELECT 1-2 AUTOMATIC 3)   3,43 3,34 3,32 3,17 3,12 3,11 3,09
Sound pressure dB(A) 49 49 50 51 54 57 57
Sound power dB(A) 81 81 82 83 86 89 89
  MODEL   280 2100 2130 4160 4200 4260 4320
  Scroll/step compressor no. 2/2 2/2 2/2 4/4 4/4 4/4 4/4
  Contours no. 2 2 2 2 2 2 2
  Power supply V-Ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
  DIMENSIONS   280 2100 2130 4160 4200 4260 4320
  L - Width mm 2600 2600 3700 3700 4800 4800 4800
  H - Height mm 2000 2000 2000 2000 2030 2030 2030
  P - Depth mm 2090 2090 2090 2090 2090 2090 2090
  SEASONAL ENERGY INDICATORS   280 2100 2130 4160 4200 4260 4320
  TXAETY MODEL SEASONAL HEATING PERFORMANCE CHARACTERISTICS                
Pdesignh (EN 14825) kW 77 98 124 153 201 252 314
SCOP (EN 14825)   3,99 3,85 3,81 3,46 3,41 3,37 3,36
ηs % 157 151 149 136 133 132 131
  TXAESY MODEL SEASONAL PERFORMANCE CHARACTERISTICS FOR HEATING                
Pdesignh (EN 14825) kW 75 95 121 148 196 246 305
SCOP (EN 14825)   4,1 3,92 3,91 3,52 3,48 3,44 3,43
ηs % 161 154 153 138 136 135 134


Data under the following conditions:
Air: 35°C - Water: 12/7°C.
Air: 7°C B.S. - 6°C B.U. - Water: 40/45°C.
Evaporator water: 12/7°C. Recovery outlet water: 45°C - Nominal flow. (Gross heating value)
In an open field (Q = 2) at 10 m from the unit.
Total sound power level in dB(A) based on measurements according to standard UNI EN-ISO 9614.
Performance data according to EN 14511:2018.
T.E.R.: Overall Efficiency
Average climate conditions, low temperature operation (35°C)
Seasonal energy efficiency: low-temperature heating in Average climate conditions (Regulations (EU) Nos. 811/2013 and 813/2013)

For more information, please contact ECS Group specialists.