ВЕНТИЛЯТОР ДЫМОУДАЛЕНИЯ CBDT

DESCRIPTION

Smoke extraction fans 400°C/2h - 300°C/2h - 200°C/2h.

CBDT: Direct-drive, double-inlet extractor units and centrifugal extractor fans, built-in, for operation in fire hazard zones 400°C/2h and 300°C/2h. Available with a single-phase motor.

Fan:

  • Galvanized sheet steel casing.
  • Impeller with forward-curved blades made of galvanized sheet steel.
  • External terminal box.
  • Vibration damper (CJBDT).
  • Complies with EN 12101-3:2002, certificate no. 370-CPD-0580.

Engine:

  • Class H motors, continuous (S1) and emergency (S2) operation, with ball bearings, IP55 protection rating, 1- or 2-speed depending on the model.
  • Single-phase 230V – 50Hz, three-phase 230/400V – 50Hz (up to 4 hp) and 400/690V – 50Hz (above 4 hp).
  • Maximum air temperature: Operation mode S1 (–20°C...+60°C), continuous. Operation mode S2 (300°C/2h, 400°C/2h).

Coating:

  • Anti-corrosion galvanized sheet steel.

Detailed information can be found on the manufacturer's website at the link www.sodeca.com or contact our specialists.