ROOF-TOP Combi

DESCRIPTION

This "COMBI" series of Roof Tops is a stand-alone, monoblock, multifunctional air conditioner for outdoor installation. It is designed for heating, ventilation, and air conditioning of large spaces. In heating mode, it operates with a gas or liquid fuel fan burner. Hermetic scroll compressors are used for cooling. The Roof Top COMBI features a supporting aluminum frame and a double sandwich panel made of galvanized and painted sheet metal with high-density mineral wool insulation and internal insulation of galvanized thermal insulation plates. The heating section contains a combustion chamber and a heat exchanger.

Key benefits:

  • Compact dimensions
  • Independent hot and cold air paths
  • Partial load capacity is based on the programmed temperature
  • Fully automatic control
  • Low power consumption of installed motors
  • Various burner fuel sources (methane, propane, liquid fuel)
  • Additionally: low NOx emissions
  • Fans are equipped with a belt drive with adjustable pulleys.
  • Hermetic compressors with safety mechanisms.
  • Efficient filtration thanks to a large filter element surface area.
  • Low maintenance costs.
  • Units can be used both indoors and outdoors.
  • Extremely low noise levels.

Main technical characteristics

Model GC 35 GC 65 GC 80 GC 100 GC 150 GC 200
Nominal air flow [m3/h] 4300 7900 1000 11500 18000 24500
Available air pressure [Pa] 250 300
Nominal heat capacity [kW] 45 83,7 104,7 128,6 192,1 257,8
Efficiency [%] 90,4 90,3 91,2 90,4 90,2 90,2
Max heating power at the output [kW] 40,7 75,6 95,3 116,3 173,3 232,6
Min. output heating power (gas) [kW] 30,6 48,8 50 50 50 60
Min. output heating power (liquid fuel) [kW] 26 60,2 60,2 89 110 154
ΔT in the heating module [°C] 28,07 28,38 28,26 29,99 28,55 28,15
Min ΔT (gas) [°C] 21,2 18,4 15 13 8,3 7,3
Min ΔT (liquid fuel) [°C] 18 22,7 18 23,1 18,2 18,8
Cooling capacity at 35°C 1) [kW] 25,3 44,7 60,5 65,5 107,8 141,4
Cooling capacity at 30°C 2) [kW] 27,1 47,8 64,7 70,1 115,3 151,2
Allowable cooling capacity at 35°C 1) [kW] 17,7 31,3 42,4 46,2 75,5 99
Min cooling capacity at 35°C 1) [kW] - 22,3 30,3 32,8 53,9 70,7
Sound pressure [dB(A)] 57 58 60 61 63 65
Supply voltage   400V/~3/50Hz
Power consumption
- compressors [kW] 6,34 12,68 15,6 17,92 27,12 39,6
- fan motors [kW] 1,5 2,2 3 4 5,5 11
Dimensions Height [mm]
Width [mm]
Depth [mm]
1355
2500
1200
1525
2980
1600
1775
3280
1900
1775
3280
1900
1925
3520
2150
2075
4000
2300
Weight [kg] 670 960 1200 1220 1600 2080
1) Supply air 27°C, 50% r.h. Outside air +35°C, operating conditions -30°C/+45°C
2) Supply air 27°C, 50% r.h. Outside air +30°C, operating conditions -30°C/+45°C

 

Detailed information can be found on the manufacturer’s website at www.cmtclima.com or contact our specialists.