Design Features:
| MODEL THHEY | 105 | 107 | 109 | 112 | ||
|---|---|---|---|---|---|---|
| ❶ | Thermal power | kW | 6,58 | 8,1 | 10,9 | 14 |
| ❶ | Power consumption | kW | 2,08 | 2,8 | 3,35 | 4,5 |
| ❶ | C.O.P. | 3,16 | 2,89 | 3,03 | 3,1 | |
| ❷ | Thermal power | kW | 7,5 | 9,7 | 12,7 | 15 |
| ❷ | Power consumption | kW | 1,6 | 2,1 | 2,72 | 3,33 |
| ❷ | C.O.P. | 4,68 | 4,61 | 4,67 | 4,51 | |
| ❸ | Thermal power (geothermal) | kW | 5,4 | 7,3 | 9,4 | 11,3 |
| ❸ | Power consumption (geothermal) | kW | 1,5 | 2,15 | 2,78 | 3,34 |
| ❸ | C.O.P. (geothermal) | 3,62 | 3,39 | 3,38 | 3,39 | |
| ❹ | Cooling capacity | kW | 5,3 | 6,8 | 9,2 | 11,9 |
| ❹ | Power consumption | kW | 1,6 | 2,19 | 2,79 | 3,67 |
| ❹ | E.E.R. | 3,31 | 3,11 | 3,3 | 3,24 | |
| ❺ | Sound pressure | dB(A) | 49 | 51 | 51 | 53 |
| Scroll/step compressor | n. | 1/1 | 1/1 | 1/1 | 1/1 | |
| Water content in the storage tank KA | l | 20 | 20 | 30 | 30 | |
| ❹ | Useful head of the circulation pump | kPa | 47 | 55 | 82 | 77 |
| Power supply | V-Ph-Hz | 230-1-50 | 230-1-50 / 400-3-50 | 230-1-50 / 400-3-50 | 230-1-50 / 400-3-50 | |
| DIMENSIONS AND WEIGHT | 105 | 107 | 109 | 112 | ||
| L - Width | mm | 585 | 585 | 660 | 660 | |
| H - Height (equipment PUMP - НАСОС) | mm | 535 | 535 | 535 | 535 | |
| H - Height (equipment PUMP+KA - НАСОС+KA) | mm | 855 | 855 | 855 | 855 | |
| P - Depth | mm | 386 | 386 | 420 | 420 | |
| ❻ | Weight | kg | 78 | 83 | 94 | 97 |
| Weight KA | kg | 28 | 28 | 33 | 33 |
Data under the following conditions:
❶ Hot water: 40/45°C - Evaporator water: 10/7°C.
❷ Hot water: 30/35°C - Evaporator water: 10/7°C.
❸ Hot water: 30/35°C - Evaporator water: 0/-3°C, 30% glycol
❹ Chilled water: 12/7°C - Condenser water: 30/35°C.
❺ In an open area (Q = 2) at a distance of 1 m from the unit.
❻ Weight refers to the most complete configuration.
Performance data according to EN 14511:2018.
KA = Accumulator tank.
KTC = Connection pipe.