ТЕПЛОВОЙ НАСОС COMPACT-ID TCCITY-THCITY 117÷128

DESCRIPTION

RHOSS EXP ISO 9001RHOSS EXP EUROVENT

Design Features:

  • Compressor: Hermetically sealed rotary scroll compressor with thermal protection and crankcase heating element, driven by an inverter;
  • Water-side heat exchanger: Stainless steel fins with appropriate insulation, including an anti-freeze heating element and a differential pressure switch for water flow;
  • Air-side heat exchanger: finned coil with copper tubes and aluminum fins for TCCITY and with a hydrophilic treatment for THCITY, including protective grilles;
  • Fan: Plug-Fan electric fan with a directly connected, low-consumption EC motor, internal thermal protection, and protective grilles. Removable fan section for on-site installation;
  • Vertical condensing air supply; horizontal supply can be easily configured on-site;
  • Electronic device for proportional fan speed control down to an outside temperature of -15°C when operating in cooler mode and up to an outside temperature of 40°C when operating in heat pump mode;
  • Control: Electronic, microprocessor-based, with Adaptive Function Plus logic system;
  • Construction: Galvanized and painted galvanized steel, includes a condensate collection tray and an anti-icing heating element for the THCITY base unit.

The unit also includes:

  • Outside air temperature sensor for setpoint compensation;
  • Electronic expansion valve;
  • High and low pressure display in the refrigerant circuit;
  • Master/Slave control for up to 4 units in parallel;
  • Clock clock board.

PUMP EQUIPMENT:

  • Pump unit, including: an EC circulation pump with a 3-speed switch or continuous speed control, or an electric pump, a membrane expansion tank, a manual air bleed valve, a safety valve, and a pressure gauge.

TANK&PUMP EQUIPMENT:

  • The pump unit is equipped with the following components: an inert accumulation tank, a circulation pump or electric circulation pump, a membrane expansion tank, a manual air bleed valve, a safety valve, and a pressure gauge.
  MODEL TCCITY   117 124 128
MIN/NOM/MAX cooling capacity kW 16,4 24,3 27,5
NOM power consumption kW 5,24 8,15 9,01
E.E.R. NOM   3,13 2,98 3,05
  MODEL THCITY   117 124 128
MIN/NOM/MAX thermal power kW 17,7 24,3 28,5
NOM power consumption kW 5,33 7,48 8,88
C.O.P. NOM   3,32 3,25 3,21
MIN/NOM/MAX thermal power kW 18,8 25 29,1
NOM power consumption kW 4,59 6,1 7,28
C.O.P. NOM   4,1 4,1 4
MIN/NOM/MAX thermal power kW 12,3 18,1 22,9
NOM power consumption kW 4,14 6,65 7,46
C.O.P. NOM   2,97 2,72 3,07
MIN/NOM/MAX cooling capacity   16,2 23,8 27
E.E.R. NOM   2,98 2,84 2,91
  MODEL TCCITY-THCITY   117 124 128
Fan sound pressure dB(A) 53 53 56
Sound pressure of the casing dB(A) 42 42 45
  Nominal fan flow mmm³/h 7600 7600 8640
  Useful static pressure of the fan Pa 80 80 80
Useful head of the circulation pump P0 kPa 89 89 76
  Water content in the storage tank l 110 110 110
  Power supply V-Ph-Hz 400-3-50 400-3-50 400-3-50
  DIMENSIONS AND WEIGHT   117 124 128
  L - Width (equipment PUMP - НАСОС) mm 1522 1522 1522
  L - Width (equipment TANK&PUMP - БАК+НАСОС) mm 1625 1625 1625
  H - Height (equipment PUMP - НАСОС) mm 1280 1280 1280
  H - Height (equipment TANK&PUMP - БАК+НАСОС) mm 1590 1590 1590
  P - Depth (equipment PUMP - НАСОС) mm 815 815 815
  P - Depth (equipment TANK&PUMP - БАК+НАСОС) mm 815 815 815
Weight (equipment PUMP - НАСОС) kg 275 285 295
Weight (equipment TANK&PUMP - БАК+НАСОС) kg 445 455 465


Data under the following conditions:
❶    Air: 35°C - Water: 12/7°C.
❷    Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.
❸    Air: 7°C, D.B. - 6°C W.B. - Water: 30/35°C.
❹    Air: -7°C, D.B. - Water: 30/35°C.
❺    In the open field (Q = 2) at a distance of 5 m from the unit.
❻    Weight refers to the most complete configuration.
Performance data according to EN 14511:2018.


For more detailed information, please contact ECS Group specialists.