Advantages:
Design Features:
| MODEL TXAEY | 133 | 245 | 250 | 260 | 265 | ||
|---|---|---|---|---|---|---|---|
| ❶ | Cooling capacity (AUTOMATIC 1) | kW | 33,8 | 42,4 | 50,3 | 57,9 | 61,6 |
| ❸ | Heat recovery capacity (AUTOMATIC 2) | kW | 44,5 | 54,7 | 65,3 | 72,2 | 81,5 |
| ❷ | Thermal rated power (SELECT 1-2 AUTOMATIC 3) | kW | 39,4 | 48,1 | 56,2 | 62,5 | 68,3 |
| ❶ | Power consumption (AUTOMATIC 1) | kW | 13,5 | 17 | 18,8 | 21,9 | 24,4 |
| ❸ | Power consumption (AUTOMATIC 2) | kW | 11,8 | 13,9 | 15,8 | 17,5 | 19,4 |
| ❷ | Power consumption (SELECT 1-2 AUTOMATIC 3) | kW | 13,6 | 16,8 | 18,9 | 20,9 | 23,7 |
| ❸ | T.E.R. (AUTOMATIC 2) | 6,57 | 6,88 | 7,26 | 7,28 | 7,42 | |
| ❹ | Sound pressure | dB(A) | 54 | 56 | 56 | 57 | 57 |
| ❹ | Sound pressure of soundproofing performance | dB(A) | 51 | 53 | 53 | 54 | 54 |
| Scroll/step compressor | no. | 1/1 | 2/1 | 2/1 | 2/1 | 2/1 | |
| Contours | no. | 1 | 1 | 1 | 1 | 1 | |
| Power supply | V-Ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |
| DIMENSIONS AND WEIGHT | 133 | 245 | 250 | 260 | 265 | ||
| L - Width | mm | 1660 | 2315 | 2315 | 2315 | 2315 | |
| H - Height | mm | 1570 | 1570 | 1570 | 1570 | 1570 | |
| P - Depth | mm | 1000 | 1000 | 1000 | 1000 | 1000 | |
| Weight TXAEY | kg | 470 | 735 | 775 | 795 | 825 | |
| SEASONAL ENERGY INDICATORS | 133 | 245 | 250 | 260 | 265 | ||
| TXAEY MODEL SEASONAL HEATING PERFORMANCE CHARACTERISTICS | |||||||
| ③ | Pdesignh (EN 14825) | kW | 39 | 48 | 56 | 62 | 68 |
| ③ | SCOP (EN 14825) | 3,28 | 3,72 | 3,74 | 3,79 | 3,73 | |
| ④ | ηs | % | 128 | 146 | 147 | 149 | 146 |
| ④ | Energy efficiency class | A+ | A+ | A+ | A+ | A+ |
Data under the following conditions:
❶ Air: 35°C - Water: 12/7°C.
❷ Air: 7°C B.S. - 6°C B.U. - Water: 40/45°C.
❸ Evaporator water: 12/7°C. Water leaving the recovery unit: 45°C - Nominal flow (Gross heating value).
❹ In an open field (Q = 2) at a distance of 5 m from the unit.
Performance according to EN 14511:2018.
T.E.R.: Overall Efficiency
③ Average climate conditions, low temperature application (35°C)
④ Seasonal energy efficiency: low temperature heating in Average climate conditions (Regulations (EU) N°811/2013 and N°813/2013)
For more detailed information, please contact ECS Group specialists..