ТЕПЛОВОЙ НАСОС COMPACT-Y NF PLUS THAETY 115÷127 NF

DESCRIPTION

RHOSS EXP ISO 9001RHOSS EXP EUROVENT

Advantages:

  • Operates at outside temperatures down to –15°C;
  • Produced water temperature up to 60°C
  • Plug-and-Play unit with integrated hydraulic module;
  • Evaporation/condensation control included.

Design Features:

  • Compressor: Hermetic, scroll-type, with thermal protection and crankcase heating element for model 127;
  • Water-side heat exchanger: Stainless steel plates with appropriate insulation, including an anti-freeze heating element and a differential pressure switch for water flow;
  • Air-side heat exchanger: finned coil with copper tubes and hydrophilic-treated aluminum fins, complete with protective grilles;
  • Fan: axial-type electric fans with external rotor, equipped with internal thermal protection, protective grilles, and an electronic proportional device for continuous fan speed adjustment;
  • Control: electronic microprocessor-based control with Adaptive Function Plus logic system;

Construction: Made of galvanized and painted steel. Includes a condensate collection tray and an anti-freeze heating element in the base of the unit.

Version: T - High-efficiency/high-temperature version.

PUMP EQUIPMENT:

  • The pump unit is equipped with the following devices: a circulation pump or a circulation electric pump, a membrane expansion tank, a manual air bleed valve, a safety valve, and a pressure gauge.

TANK&PUMP EQUIPMENT:

  • The pump unit is equipped with the following components: an inert accumulation tank, a circulation pump or electric circulation pump, a membrane expansion tank, a manual air bleed valve, an automatic air bleed valve, a safety valve, and a pressure gauge.
  MODEL THAETY NF   115 117 122 124 127
Thermal power kW 16,6 17,7 23,4 25,9 30,4
Power consumption kW 5,72 6,32 8,18 9,08 10,03
C.O.P.   2,9 2,8 2,86 2,85 3,03
Thermal power kW 18 19 24,8 27,8 32,3
Power consumption kW 4,33 4,53 5,9 6,59 7,58
C.O.P.   4,16 4,19 4,2 4,22 4,26
Thermal power kW 11,7 12 15,7 17,9 20,8
C.O.P.   2,77 2,77 2,8 2,77 2,84
Cooling capacity kW 15,5 17,6 22,5 23,9 26,6
Power consumption kW 5,81 6,62 8,14 9,45 10,11
E.E.R.   2,67 2,66 2,75 2,53 2,63
Sound pressure dB(A) 50 50 52 52 53
Sound pressure of soundproofing performance dB(A) 46 46 49 49 50
Compressor spiral/stepped n. 1/1 1/1 1/1 1/1 1/1
Water content in the storage tank l 35 35 45 45 45
Nominal useful head of the circulation pump Р0/electric pump P1 kPa 75/147 64/136 66/131 69/130 63/116
Power supply V-Ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHT   115 117 122 124 127
L - Width (equipment PUMP - НАСОС) mm 1230 1230 1230 1230 1535
L - Width (equipment TANK&PUMP - БАК+НАСОС) mm 1522 1522 1522 1522 1822
H - Height mm 1090 1090 1280 1280 1510
P - Depth mm 580 580 600 600 695
Weight kg 215 225 278 288 320


Data under the following conditions:
❶    Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.
❷    Air: 7°C, D.B. - 6°C W.B. - Water: 30/35°C.
❸    Air: -7°C, D.B. - Water: 30/35°C.
❹    Air: 35°C - Water: 12/7°C.
❺    In an open area (Q = 2) at a distance of 5 m from the unit.
❻    Weight refers to the most complete configuration.
Performance data according to EN 14511:2018. Complete with electric pump.
Note:
- The unit is not suitable for radiant cooling operation with a circulation pump (P0/ASP0 option).
 - The permissible heat exchanger temperature difference is ΔT = 4-8°C.


For more detailed information, please contact ECS Group specialists.