Advantages:
Design Features:
Construction: Made of galvanized and painted steel. Includes a condensate collection tray and an anti-freeze heating element in the base of the unit.
Version: T - High-efficiency/high-temperature version.
PUMP EQUIPMENT:
TANK&PUMP EQUIPMENT:
| MODEL THAETY NF | 115 | 117 | 122 | 124 | 127 | ||
|---|---|---|---|---|---|---|---|
| ❶ | Thermal power | kW | 16,6 | 17,7 | 23,4 | 25,9 | 30,4 |
| ❶ | Power consumption | kW | 5,72 | 6,32 | 8,18 | 9,08 | 10,03 |
| ❶ | C.O.P. | 2,9 | 2,8 | 2,86 | 2,85 | 3,03 | |
| ❷ | Thermal power | kW | 18 | 19 | 24,8 | 27,8 | 32,3 |
| ❷ | Power consumption | kW | 4,33 | 4,53 | 5,9 | 6,59 | 7,58 |
| ❷ | C.O.P. | 4,16 | 4,19 | 4,2 | 4,22 | 4,26 | |
| ❸ | Thermal power | kW | 11,7 | 12 | 15,7 | 17,9 | 20,8 |
| ❸ | C.O.P. | 2,77 | 2,77 | 2,8 | 2,77 | 2,84 | |
| ❹ | Cooling capacity | kW | 15,5 | 17,6 | 22,5 | 23,9 | 26,6 |
| ❹ | Power consumption | kW | 5,81 | 6,62 | 8,14 | 9,45 | 10,11 |
| ❹ | E.E.R. | 2,67 | 2,66 | 2,75 | 2,53 | 2,63 | |
| ❺ | Sound pressure | dB(A) | 50 | 50 | 52 | 52 | 53 |
| ❺ | Sound pressure of soundproofing performance | dB(A) | 46 | 46 | 49 | 49 | 50 |
| Compressor spiral/stepped | n. | 1/1 | 1/1 | 1/1 | 1/1 | 1/1 | |
| Water content in the storage tank | l | 35 | 35 | 45 | 45 | 45 | |
| ❹ | Nominal useful head of the circulation pump Р0/electric pump P1 | kPa | 75/147 | 64/136 | 66/131 | 69/130 | 63/116 |
| Power supply | V-Ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |
| DIMENSIONS AND WEIGHT | 115 | 117 | 122 | 124 | 127 | ||
| L - Width (equipment PUMP - НАСОС) | mm | 1230 | 1230 | 1230 | 1230 | 1535 | |
| L - Width (equipment TANK&PUMP - БАК+НАСОС) | mm | 1522 | 1522 | 1522 | 1522 | 1822 | |
| H - Height | mm | 1090 | 1090 | 1280 | 1280 | 1510 | |
| P - Depth | mm | 580 | 580 | 600 | 600 | 695 | |
| ❻ | Weight | kg | 215 | 225 | 278 | 288 | 320 |
Data under the following conditions:
❶ Air: 7°C D.B. - 6°C W.B. - Water: 40/45°C.
❷ Air: 7°C, D.B. - 6°C W.B. - Water: 30/35°C.
❸ Air: -7°C, D.B. - Water: 30/35°C.
❹ Air: 35°C - Water: 12/7°C.
❺ In an open area (Q = 2) at a distance of 5 m from the unit.
❻ Weight refers to the most complete configuration.
Performance data according to EN 14511:2018. Complete with electric pump.
Note:
- The unit is not suitable for radiant cooling operation with a circulation pump (P0/ASP0 option).
- The permissible heat exchanger temperature difference is ΔT = 4-8°C.
For more detailed information, please contact ECS Group specialists.