+38 044 379-12-05, (-07)

+38 044 379-12-05, (-07)

+38 044 379-12-05, (-07)

ТЕПЛОВОЙ НАСОС EASYPACK TCAEY-THAEY 269÷2146

DESCRIPTION

RHOSS EXP ISO 9001RHOSS EXP EUROVENT

A wide range of components and accessories:

  • Polyvalent system for 2-pipe units + ACS (with RC100 option);
  • Built-in master/slave control board functionality;
  • Model HT65 for producing 65°C water (°).

Design Features:

  • Compressor: Hermetically sealed rotary scroll compressor with thermal protection and crankcase heating element;
  • 3-stage regulation with high efficiency at partial loads;
  • Water heat exchanger: with stainless steel plates, closed-cell polyurethane foam rubber insulation, and a differential water flow pressure switch;
  • Air heat exchanger: with microchannels or a finned coil with copper tubes and aluminum fins, depending on the model/size;
  • Fan: Axial external rotor electric fans with internal thermal protection and protective grilles;
  • Control: Electronic, microprocessor-based, with Adaptive Function Plus logic system;
  • Construction: The supporting structure is made of galvanized sheet steel, coated with polyester powder paint.

The unit also includes:

  • thermal-magnetic switches, compressors, and fans;
  • refrigerant circuit high and low pressure display;
  • Master/Slave control for up to 4 units in parallel;
  • clock circuit board.

Versions:

  • B - Basic version (TCAEBY);
  • Т - High-efficiency version with an enlarged condensate section (TCAETY-THAETY);
  • S - Soundproofed version, includes soundproofing for the technical compartment, low-speed fans, and an enlarged condensate section (TCAESY-THAESY);
  • Q - Enhanced soundproofing version, includes soundproofing for the compressor technical compartment, ultra-low-speed fans, and an enlarged condensate section (TCAEQY-THAEQY).

Models:

  • TCAEBY: Basic version designed for cooling only;
  • TCAETY: High-efficiency unit designed for cooling only;
  • TCAESY: Soundproofed unit designed for cooling only;
  • TCAEQY: Enhanced soundproofed unit designed for cooling only;
  • THAETY: heat pump unit;
  • THAESY: low-noise heat pump unit;
  • THAEQY: high-noise heat pump unit.
  MODEL TCAEBY   269 279 289 296 2112 2125 2146
Cooling capacity kW 65,6 72,1 77,6 86,5 105,5 - -
E.E.R.   2,74 2,81 2,81 2,62 2,79 - -
Power consumption kW 23,94 25,66 27,62 33,02 37,81 - -
  MODEL TCAETY-TCAESY-TCAEQY   269 279 289 296 2112 2125 2146
Cooling capacity kW 69,2 79,1 90,1 96,1 112 125,5 144,4
Cooling capacity kW 67,7 76,7 87,6 92,1 108 122 138,9
Cooling capacity kW 64,7 71,2 84,6 89,6 101,1 116,5 131
E.E.R.   3,12 3,18 3,12 3,11 3,1 3,12 3,12
E.E.R.   2,92 3,05 2,95 2,92 2,94 2,99 2,94
E.E.R.   2,82 2,72 2,8 2,72 2,53 2,72 2,59
Power consumption kW 22,18 24,87 28,88 30,9 36,13 40,22 46,28
Power consumption kW 23,18 25,15 29,69 31,54 36,73 40,8 47,24
Power consumption kW 22,94 26,18 30,21 32,94 39,96 42,83 50,58
  MODEL THAETY-THAESY-THAEQY   269 279 289 296 2112 2125 2146
Thermal rated power kW 73,4 82,4 92,4 100,5 118,5 133,1 151,7
Thermal rated power kW 70,8 80,4 90,4 98 115 129,1 147,6
Thermal rated power kW 70,3 77,3 88,4 95,4 111 125,5 143,6
C.O.P.   3,35 3,36 3,31 3,28 3,31 3,25 3,23
C.O.P.   3,32 3,36 3,31 3,29 3,3 3,27 3,27
C.O.P.   3,31 3,3 3,27 3,26 3,21 3,23 3,22
Cooling capacity kW 67,2 76,7 86,6 93,6 107,5 121,5 139,4
Cooling capacity kW 66,2 74,7 85,7 89,6 104,6 119 136,9
Cooling capacity kW 63,7 69,7 82,7 86,6 99,1 112,1 128,5
Power consumption kW 21,91 24,52 27,92 30,64 35,8 40,95 46,97
Power consumption kW 21,33 23,93 27,31 29,79 34,85 39,48 45,14
Power consumption kW 21,24 23,42 27,03 29,26 34,58 38,85 44,6
  MODEL TCAEY-THAEY   269 279 289 296 2112 2125 2146
TCAEBY sound pressure dB(A) 50 50 50 50 52 - -
TCAETY-THAETY sound pressure dB(A) 50 51 51 51 53 54 54
TCAESY-THAESY sound pressure dB(A) 46 47 47 47 49 50 50
TCAEQY-THAEQY sound pressure dB(A) 42 42 43 43 46 47 47
TCAEBY sound power dB(A) 82 82 82 82 84 - -
TCAETY-THAETY sound power dB(A) 82 83 83 83 85 86 86
TCAESY-THAESY sound power dB(A) 78 79 79 79 81 82 82
TCAEQY-THAEQY sound power dB(A) 74 74 75 75 78 79 79
  Scroll/step compressor n. 2/3 2/3 2/3 2/3 2/3 2/3 2/3
  Contours n. 1 1 1 1 1 1 1
  Power supply V-Ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
  DIMENSIONS AND WEIGHT   269 279 289 296 2112 2125 269
  L - Version width B mm 2650 2650 2650 2650 3250 - -
  L - Version width T - S - Q mm 3250 3250 3250 3250 3450 3450 3450
  H - Height of version B mm 1700 1700 1700 1700 1700 - -
  H - Height of version T - S mm 1700 1700 1700 1700 2000 2000 2000
  H - Height of version Q mm 1520 1520 1520 1520 2000 2000 2000
  P - Version depth B mm 1210 1210 1210 1210 1210 - -
  P - Version depth T - S - Q mm 1210 1210 1210 1210 1520 1520 1520
Weight TCAEBY kg 755 760 795 800 980 - -
Weight TCAETY kg 850 865 870 905 1160 1195 1255
Weight THAETY kg 915 930 935 980 1240 1280 1355


Data under the following conditions:
❶    Air: 35°C - Water: 12/7°C.
❷    Air: 7°C, D.B. - 6°C W.B. - Water: 40/45°C.
❸    In an open field (Q = 2) at a distance of 10 m from the unit.
❹    Total sound power level in dB(A) based on measurements according to UNI EN-ISO 9614.
❺    Weight of empty unit.
TCAESY-THAESY silent version.
TCAEQY-THAEQY super silent version.
Performance according to EN 14511:2018.


For more detailed information, please contact ECS Group specialists.