Smoke extraction fans: 400°C/2h – 300°C/2h – 200°C/2h.
TCR/R: Heavy-duty centrifugal exhaust fans for outdoor use in fire-hazard zones, with a fire resistance rating of 400°C/2h, single-inlet design, fitted with an impeller featuring backward-curved blades.
- TCR/R: Heavy-duty centrifugal exhaust fans for outdoor use in fire-hazard zones, with a fire resistance rating of 400°C/2h, single-inlet, fitted with an impeller with backward-curved blades.
- CJTCR/R: Heavy-duty single-inlet exhaust units, fire resistance rating 400°C/2h, sound-insulated casing, for operation outside fire-hazard zones.
Fan:
- Sheet steel casing.
- High-strength impeller with backward-curved blades, made of sheet steel, coated with heat-resistant paint.
- Complies with standard EN-12101-3-2002, certificate no.: 0370-CPD-0400 (TCR/R), and no.: 0370-CPD-0401 (CJTCR/R).
Engine:
- Class F motors with ball bearings, IP55 protection, 1- or 2-speed depending on the model.
- Three-phase 230/400V – 50Hz (up to 5.5 hp) and 400/690V – 50Hz (over 5.5 hp).
- Maximum air temperature:
- Duty cycle S1 (–20°C...+120°C), continuous.
- Duty cycle S2: 200°C/2h, 300°C/2h, 400°C/2h.
Coating:
- Anti-corrosion coating based on polyester resin (polymerises at 190°C after degreasing with an alkaline solution and pre-treatment with a phosphate-free solution).
Detailed information can be found on the manufacturer's website at the link www.sodeca.com or contact our specialists.